*Real-time monitor combine with branch way inspection, guarantee the real-time of monitor;
*Used in high voltage DC 240V/380V power supply system, system has high accuracy: bus voltage to ground is better than 0.2%, bus and branch ways's resistance to ground is better than 5% (less than 50k);
*Detection range is large: it can detect at most 100k resistance;
*Fast response time: bus is 5s, branch way is 20s;
*RS485 serial port communication with monitor PC. The PC communication protocol can be customized, it convenient for other factory to connect with the monitor;
*Through the monitor can set the alarm limit, adapted to different local climate conditions; can monitor the fall situation of positive and negative bus insulation value etc.; 
*Cancelled to inject the low frequency AC signal, branch way detection are not affected by bus to ground capacitance;
*Innovative isolation intelligent leakage current sensor, vulnerable circuit uninterrupted power supply replacement design scheme, effectively solve the problem that DC sensor damage cannot be replaced with power supply;
*EMS performance conforms to the IEC61000-6-2 industrial environment anti-interference standards;
*Products conforms to the IEC61000-6-2 ROHS lead-free standard, through the CE certification.

JYCL2.5 Insulation Monitor

Function Items Parameter

Parameter Range

Grade

Note

Power Supply

180~420VDC or 130~264VAC

Shared port with

bus voltage detection

system’s

Power Consumption

<15w

Match with less than 20

branch way sensors

Working Environment Temperature

-10~+50

Working Relative Humidity

10%RH~90%RH

Atmospheric Pressure

70~106kpa

Machine Dimension(L)×(W)×(H)

216mm×94mm×38.5mm

Weight

About910g

Communi cation Interface

RS485

Communication Baud Rate

12004800960019200bps can be set

Bus Voltage To Ground Measurement 

0~450V

±0.2%

Bus Insulation Resistance Measurement

0~100K

±2%

Branch Way Insulation Resistance Measurement

0~75K

±4%

Our company supply the intelligent

leakage current sensor to accomplish

Auxiliary power output

+12V,1000mA

Insulation resistance alarm threshold

5~25K

Default:25k

Two way dry contact output

Contact capacity:DC30V/1A,

AC125V/0.5A,switch power:30W

Provide two way mutual

exclusion output

Purchase:JYCL2.5 Insulation Monitor

Company name

Your Name

Telephone

E-mail

Purchasing intention description
Verification Code