Characteristics
Parameter
Model type
Structure
Wiring
*Hall open-loop operational principle, can measure current in any waveform, the output terminal can reflect the waveforms parameters of input current
*Controlled by temperature compensation circuit, measure accurately
*Perforation input, standard din rail(35mm) mounting
*The measuring head can be rotated, it is convenient to thread wire from different angle
*It widely applies to all kinds of industrial current online detection system
*Dimension:(mm):95(L)×37(W)×88.5(H) aperture:22mm
*Standards : IEC688:1992, QB/LF2007-1
Input Range :0~400A can choose 0~50A,0~100A etc
Accuracy Grade:≤1.0%.F.S
Linearity Degree :Better than 0.2%
*Response Time:≤10uS
*Frequency: 0~10KHZ
*Offset Voltage:≤20mV
*Flame Retardancy:UL94-V0
*Temperature Characteristics :≤150PPM/℃(0~50℃)
*Power Consumption:≤30mA+output current
*Isolation Withstanding Voltage AC2.0KV/min*1mA between input/output/ power
*Load Capacity 2 times current continuous, 30 times 1 second
*Working Environment: -10℃~50℃,20%~90% without condensation
*Storage Environment: -40℃~70℃,20%~95% without condensation
A--- Output |
B---Power supply 2: 12V±10% 2: 15V±10% 4: 24V±15% 5: ±12V±10% |
C---Current input range |
Model selection1: LF-DI12-15A2-1.0/0~100A |
Explanation: this product is a 0~100A input range, 0~5V tracking output, ±12V power supply, A2 style 1-way DC current transducer. |